CC-PFB802 51454953-176 Honeywell Experion PKS FIM8 Fieldbus Interface Module
CC-PFB802 51454953-176
Series C FIM8 interface module providing eight 31.25 kbit/s FOUNDATION Fieldbus H1 links for an Experion PKS control architecture. Confirm the exact installed configuration and revision before replacement.
Scope note: Supplied as a model-specific industrial component; system engineering, accessories and site acceptance are verified separately.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales1@amikon.cnWhatsapp/Mob:
+86 18150117685FIM8 FOUNDATION Fieldbus interface module for Experion PKS Series C
This conformally coated Series C FIM8 links FOUNDATION Fieldbus H1 devices with the Honeywell Experion PKS control environment and is used with the matching IOTA and controller architecture.
The module supports eight H1 networks and may be engineered in non-redundant or redundant arrangements; actual device capacity depends on segment power, bandwidth, cable length, topology and intrinsic-safety design.
Ordering note: Verify the complete model, installed system, revision and current manufacturer documentation before purchase or installation.
| Manufacturer / platform | Honeywell Experion PKS Series C |
|---|---|
| Module type | FIM8 FOUNDATION Fieldbus interface module |
| H1 networks | Eight links at 31.25 kbit/s each |
| Architecture | Non-redundant or redundant configuration |
| Module load | 0.380 A at 25 VDC; 9.5 W dissipation |
| Macrocycle selections | 250 ms, 500 ms, 1, 2, 4, 8, 16 or 32 s |
| Published device limit | Up to 16 non-IS or 3 IS devices per H1 network, subject to segment design |
| I/O termination | Links connect through the matching coated eight-link IOTA |
Compatibility depends on the complete ordering code, installed hardware, wiring and approved engineering data.
It provides eight FOUNDATION Fieldbus H1 networks operating at 31.25 kbit/s each.
Yes, automatic redundancy is supported and fieldbus function blocks continue executing and communicating through switchover or failover.
The selectable periods are 250 ms, 500 ms, 1 s, 2 s, 4 s, 8 s, 16 s and 32 s.
Reserve 0.380 A at 25 VDC for the electronics module, corresponding to 9.5 W dissipation.
The published limit is 16 non-intrinsically-safe devices or three intrinsically safe devices per network, subject to bandwidth, current, bus length and topology.
Send the complete CC-PFB802 51454953-176 model, quantity, installed system, destination and clear label photos. Availability and condition will be confirmed before quotation.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.
Copyright @2026 SalesPlc Limited. Sitemap