CI626V1
AF100 Communication Interface · 3BSE012868R1 · Advant Controller 110 / 160
Lifecycle note: Preserve station addressing, bus configuration and both media routes. Verify communication on each coaxial line after replacement.
ItemNO:
3BSE012868R1Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 153 5940 8275AF100 Communication Interface · Advant Controller 110 / 160
ABB CI626V1 is an Advant Fieldbus 100 communication interface for Advant Controller 110 and Advant Controller 160. The selected product identity is CI626V1 / 3BSE012868R1. ABB describes the V1 interface as using coaxial connectors and an integrated modem with full redundant-media support.
The AF100 manual distinguishes CI626V1 from the earlier CI626 and from the twisted-pair CI627. The CI626-family diagrams show two BNC bus connectors and drop-cable arrangements for single or redundant coaxial media. Redundant cables improve communication availability; they do not double bandwidth.
Before exchange, record the station address, bus configuration, controller position and cable routing. Keep bus continuity and termination consistent with the approved network arrangement and check traffic on both lines after commissioning. Use the exact V1 identity when quoting a spare because the predecessor has different redundancy limitations.
| Manufacturer | ABB |
|---|---|
| Model / order number | CI626V1 / 3BSE012868R1 |
| Product function | Fieldbus communication interface |
| Communication network | Advant Fieldbus 100 (AF100) |
| Supported controller families | Advant Controller 110 and Advant Controller 160 |
| Direct transmission medium | Coaxial cable |
| Modem | Integrated |
| Media redundancy | Full redundant-media support |
| Coaxial connectors | Two BNC bus connectors in CI626-family diagrams |
| Single-media drop cable | TK518, as shown in ABB Figure 11 |
| Redundant-media drop cables | TK516, as shown in ABB Figure 12 |
| Coaxial segment length with RG59 | Up to 300 m; AF100 network design rules apply |
| Coaxial segment length with RG11 | Up to 700 m; AF100 network design rules apply |
| AC110 station-address range | 1–79; selected on the controller backplane |
Preserve station addressing, bus configuration and both media routes. Verify communication on each coaxial line after replacement.
ABB lists full redundant-media support for CI626V1. The predecessor CI626 has reduced support, including a maximum 4 m cable-length difference between any two stations on coaxial media. Preserve the V1 designation in the order.
ABB identifies CI626V1 as a coaxial interface with an integrated modem. CI627 is the separately listed twisted-pair interface. Review the network media and approved conversion arrangement rather than treating the connectors as interchangeable.
No. ABB states that redundant cables increase availability, not communication bandwidth. Plan redundancy for continuity of service and validate the two routes separately.
The ABB diagrams place drop cables and BNC T-adapters between the bus and the interface. This arrangement preserves network continuity during an approved interface exchange; keep the installed topology and termination intact.
The manual specifies an address from 1 to 79 on the controller backplane thumb-wheel switch. For the CI626 family to read this setting, the interface is installed in the second AC110 backplane slot. Follow the controller procedure when changing it.
No. ABB gives 300 m for RG59 and 700 m for RG11. These are segment limits within the complete AF100 network rules, so repeaters, media conversion and total network design still require review.
For the CI626 family, traffic indication means that the modem detects receiving or transmitting activity on a line. Confirm application data and station supervision as well; traffic alone does not prove correct process values.
Preserve the installed configuration and station identity. ABB explains that valid nonvolatile configuration is reused on restart; compare the resulting operation with the approved project and investigate missing or inconsistent configuration before returning control to service.
Send the model, complete part number, quantity, destination and nameplate photo. We will verify identification details before confirming availability and lead time.
Manufacturer PDF reference: CI626V1 / 3BSE012868R1 — ABB Manufacturer Manual. Full ABB manual; refer to the model-specific pages identified above and verify the installed hardware and configuration before use.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.