IC200ALG620
Four-Channel 16-Bit RTD Analog Input Module · Four-channel intelligent RTD input module for resistance and temperature measurement.
Lifecycle note: Use the unit nameplate and current official documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 15359408275Four-Channel 16-Bit RTD Analog Input Module · VersaMax Distributed I/O
GE IC200ALG620 is a four-channel intelligent RTD analog input module for resistance and temperature measurement in a compatible distributed I/O station.
Each channel can be configured independently for a supported three-wire or four-wire platinum, copper, nickel or nickel/iron RTD, with alarm and wiring diagnostics reported to the host.
Before replacement, verify the exact module revision, terminal base, RTD type, lead arrangement, configured scale, alarm limits and host configuration.
| Manufacturer | GE |
|---|---|
| Model | IC200ALG620 |
| Channels | 4 independent RTD inputs |
| Supported wiring | 3-wire and 4-wire RTDs |
| Digital resolution | 15 bits plus sign |
| RTD materials | Platinum, copper, nickel and nickel/iron |
| Resistance ranges | 0-500 ohms and 0-3000 ohms |
| Measurement units | 0.1 ohm, 0.1 °C or 0.1 °F |
| External power | Not required |
| Backplane current | 125 mA maximum at 5 V; 125 mA at 3.3 V |
| Update rate | About 210 ms/channel at 60 Hz; 230 ms/channel at 50 Hz |
| Isolation | 250 VAC continuous input-to-logic/frame |
| Operating temperature | 0 to 60 °C |
IC200ALG620 operates as four-channel 16-bit rtd analog input module within VersaMax Distributed I/O, and its installed role must be confirmed from the host system configuration and field wiring.
IC200ALG620 must be matched by the complete catalog number, channel or interface configuration, electrical ratings, connector arrangement and the limits listed in the technical table.
Before replacing IC200ALG620, record the slot or mounting position, wiring and terminal assignments, communication or channel settings, scaling, alarms, firmware or parameter data and the host configuration.
A similar-looking unit should not replace IC200ALG620 until the electrical function, revision, interfaces, channel count, mounting, software support and application approval are confirmed.
Installation of IC200ALG620 requires inspection of the connector and nameplate, correct supply polarity and rating, secure mounting, approved grounding and shielding, and controlled functional testing.
IC200ALG620 should be commissioned under the approved site procedure by checking diagnostics, each configured signal or network path, safe-state behavior and the response of the connected equipment.
An inquiry for IC200ALG620 should include the full nameplate and revision, host equipment, installed configuration, connector or wiring photographs, required quantity, condition requirement and destination.
Send the complete IC200ALG620 catalog number, revision, quantity, destination and nameplate photo. Identification details will be checked before quotation.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.