FC-SDIL-1608
16-Channel Fail-Safe NAMUR Input Module - Safety Digital Input Module
Lifecycle note: Use the unit nameplate and current Honeywell documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 1535940827516-Channel Fail-Safe NAMUR Input Module - Honeywell Safety Manager
Honeywell FC-SDIL-1608 is a sixteen-channel fail-safe digital input module for DIN-compatible NAMUR field sensors in Safety Manager. The documented input circuit is used with the approved BN-1608 conversion arrangement.
The module uses a 1.4 to 1.9 mA switching level, 0.2 mA +/-0.05 mA hysteresis and a first-order 100 Hz low-pass filter. Maximum field-wire resistance is 50 ohm and maximum load capacitance is 100 nF.
FC-SDIL-1608 supplies 7.9 to 8.7 V to the loop and requires 5 VDC at 160 mA plus 24 VDC at 110 mA. Verify BN-1608 pairing, sensor current characteristics, chassis keying and configured diagnostics before commissioning.
| Manufacturer | Honeywell |
|---|---|
| Complete model | FC-SDIL-1608 |
| Product type | Safety Digital Input Module |
| System family | Honeywell Safety Manager |
| Input channels | 16 |
| Input type | DIN-compatible NAMUR |
| Switch level | 1.4 to 1.9 mA |
| Hysteresis | 0.2 mA +/-0.05 mA |
| Input filter | First-order low-pass, 100 Hz |
| Field-wire resistance | 50 ohm maximum |
| Loop output voltage | 7.9 to 8.7 V |
| Loop output current | 170 mA, short-circuit proof |
| Maximum load capacitance | 100 nF |
| Power | 5 VDC 160 mA; 24 VDC 110 mA |
| Space requirement | 4 HP, 3U |
Honeywell FC-SDIL-1608 is a safety digital input module for the Honeywell Safety Manager. It converts sixteen DIN-compatible NAMUR sensor signals for the Safety Manager application.
Honeywell FC-SDIL-1608 converts sixteen NAMUR sensor currents into fail-safe digital input states for Safety Manager.
Honeywell FC-SDIL-1608 is used for proximitors and other DIN-compatible NAMUR sensors requiring monitored low-current safety inputs.
Honeywell specifies 16 channels, 1.4-1.9 mA switching, 100 Hz filtering, 50 ohm maximum field resistance and 7.9-8.7 V loop supply.
Honeywell FC-SDIL-1608 is specified in combination with BN-1608 and must match the approved chassis, FTA and sensor circuit.
Before installing Honeywell FC-SDIL-1608, verify the complete model and revision, mounting arrangement, power, field wiring, grounding and approved Safety Manager configuration.
Commission Honeywell FC-SDIL-1608 under the approved Honeywell and site procedure. Prove its configured channels, diagnostics, communications and safety response before returning the system to service.
Do not substitute a similar suffix for Honeywell FC-SDIL-1608 until the hardware revision, electrical interface, companion assembly and Safety Manager release are confirmed compatible.
Provide the complete Honeywell FC-SDIL-1608 nameplate, version, serial number, companion hardware, Safety Manager release, quantity and destination.
Send the complete model, version, quantity, destination and nameplate photo. We will verify identification before confirming availability and lead time.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.