FC-SDO-0824 V1.3
Version 1.3 Eight-Channel Fail-Safe Digital Output Module - Safety Digital Output Module
Lifecycle note: Use the unit nameplate and current Honeywell documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 15359408275Version 1.3 Eight-Channel Fail-Safe Digital Output Module - Honeywell Safety Manager
Honeywell FC-SDO-0824 V1.3 is a revision-specific eight-channel fail-safe digital output module for Safety Manager. It switches monitored 24 VDC solid-state source outputs for configured safety functions.
Base FC-SDO-0824 data specifies 550 mA maximum current, 120 mA lamp load, 1 uF maximum capacitance, less than 2.0 V drop at 500 mA and less than 0.1 mA off current.
Before replacement, verify the V1.3 nameplate, A9/C9 keying, FTA, field supply, output load, watchdog circuit and Safety Manager release.
| Manufacturer | Honeywell |
|---|---|
| Complete model | FC-SDO-0824 V1.3 |
| Product type | Safety Digital Output Module |
| System family | Honeywell Safety Manager |
| Complete identification | FC-SDO-0824 V1.3 |
| Base module | FC-SDO-0824 |
| Requested revision | V1.3 |
| Output channels | 8 |
| Output type | 24 VDC solid-state source |
| Maximum current | 550 mA |
| Maximum lamp load | 120 mA / 2.9 W |
| Maximum load capacitance | 1 uF |
| Voltage drop | Less than 2.0 VDC at 500 mA |
| Off current | Less than 0.1 mA |
| Space requirement | 4 HP, 3U |
Honeywell FC-SDO-0824 V1.3 is a safety digital output module for the Honeywell Safety Manager. It is a V1.3 eight-channel 24 VDC solid-state safety output module.
Honeywell FC-SDO-0824 V1.3 switches eight fail-safe DC outputs and monitors output-channel operation.
Honeywell FC-SDO-0824 V1.3 is used for approved 24 VDC final elements in Safety Manager applications.
The FC-SDO-0824 base specification lists eight 24 VDC source outputs rated to 550 mA with short-circuit protection.
Honeywell FC-SDO-0824 V1.3 must match the approved FTA, chassis keying, field supply and system release.
Before installing Honeywell FC-SDO-0824 V1.3, verify the complete model and revision, mounting arrangement, power, field wiring, grounding and approved Safety Manager configuration.
Commission Honeywell FC-SDO-0824 V1.3 under the approved Honeywell and site procedure. Prove its configured channels, diagnostics, communications and safety response before returning the system to service.
Do not substitute a similar suffix for Honeywell FC-SDO-0824 V1.3 until the hardware revision, electrical interface, companion assembly and Safety Manager release are confirmed compatible.
Provide the complete Honeywell FC-SDO-0824 V1.3 nameplate, version, serial number, companion hardware, Safety Manager release, quantity and destination.
Send the complete model, version, quantity, destination and nameplate photo. We will verify identification before confirming availability and lead time.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.
Copyright @2026 SalesPlc Limited. Sitemap
/ Blog
/ XML
/ Terms And Conditions
/ Privacy Policy
Network Supported