FBM219
24-Input 8-Output Discrete I/O Interface Module · Twenty-four discrete input channels plus eight discrete output channels with group isolation
Lifecycle note: Use the installed-unit identification and current manufacturer documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
[email protected]Whatsapp/Mob:
+86 1535940827524-Input 8-Output Discrete I/O Interface Module · Foxboro I/A Series
Foxboro FBM219 is a 24-Input 8-Output Discrete I/O Interface Module for Foxboro I/A Series. Twenty-four discrete input channels plus eight discrete output channels with group isolation.
Discrete field-state acquisition and switching through the specified termination assembly. The supported field-voltage and output-current ratings depend on the selected termination assembly; FBM219 is not the compact FBM219 version.
Match the FBM219 baseplate, termination assembly, field-voltage option and I/O wiring to the approved installation.
| Manufacturer | Foxboro |
|---|---|
| Model | FBM219 |
| Product type | 24-Input 8-Output Discrete I/O Interface Module |
| Product family / system | Foxboro I/A Series |
| Discrete inputs | 24 channels |
| Discrete outputs | 8 channels |
| Channel isolation | Input and output groups isolated |
| Field-voltage options | 15 to 60 V DC, 120 V AC / 125 V DC, or 240 V AC, depending on termination assembly |
| Input debounce | No filter or 4, 8, 16, or 32 ms configurable |
| Voltage-monitor ON state | 15 to 30 V DC |
| Voltage-monitor OFF state | 0 to 5 V DC |
| Module fieldbus | Redundant 2 Mbps |
Confirm current manufacturer support and installed-system requirements before replacing FBM219.
FBM219 has 24 discrete inputs and eight discrete outputs. The manufacturer specifies group isolation and a termination-assembly-dependent field interface.
The associated termination assembly determines whether the installation handles the documented DC or AC field-signal options. Do not select voltage from the FBM219 module label alone; match the exact TA and field circuit.
The FBM219 specification lists input filter time, fail-safe configuration and fallback, and sustained or momentary outputs under its Discrete I/O or Ladder Logic program. Set these to the approved control design.
The manufacturer describes 100 Series functionality when FBM219 is paired with the appropriate termination assemblies. This is a planned migration path, not proof that every older module or field wiring is a drop-in replacement.
FBM219 interfaces with the redundant 2 Mbps module Fieldbus. Confirm the baseplate, fieldbus paths and termination assembly before integrating its 24 inputs and eight outputs.
Check the TA voltage and wiring, input states and configured filter time, output action, and fail-safe behavior against the approved I/O list. Test each field circuit under the site commissioning procedure.
Provide the full FBM219 identification, exact termination-assembly part number, field-voltage and contact/relay requirements, output load, baseplate arrangement and revision.
Send the complete model, quantity, destination and nameplate photo. We will verify identification details before confirming availability and lead time.
Technical data is based on manufacturer-owned documentation for FBM219. Final suitability must be checked against the exact installed unit and current official documentation.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.