FS-TSDI-16UNI
16-Channel Universal Safe Digital Input FTA - Safety Digital Input Field Termination Assembly
Lifecycle note: Use the unit nameplate and current Honeywell documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 1535940827516-Channel Universal Safe Digital Input FTA - Honeywell Safety Manager
Honeywell FS-TSDI-16UNI is the standard-coated type number for the universal Safety Manager digital input FTA. It routes sixteen external screw-terminal circuits through SICC-0001/Lx cables to the approved SDIL-1608 input module arrangement.
The sixteen inputs are separated into two groups of eight, each protected by a 250 mA common-positive fuse. The FTA supports 24/48 VDC and NAMUR applications, while the connected input module defines the actual maximum voltage.
Honeywell specifies 90 x 70 x 60 mm dimensions and 91 mm of TS32 or TS35 rail. Confirm the FS rather than FC variant, fuse loading, channel polarity, field wiring, cable length and input-module pairing.
| Manufacturer | Honeywell |
|---|---|
| Complete model | FS-TSDI-16UNI |
| Product type | Safety Digital Input Field Termination Assembly |
| System family | Honeywell Safety Manager |
| Type number | FS-TSDI-16UNI |
| Channels | 16, two groups of eight |
| Supported input class | 24/48 VDC and NAMUR |
| Maximum voltage | 50 VDC category 3; 150 VDC category 2 |
| Fuse | 250 mA, 5 x 20 mm |
| Maximum output current per fuse | 175 mA |
| Dimensions | 90 x 70 x 60 mm |
| DIN rail | TS32 or TS35 x 7.5 |
| Used rail length | 91 mm |
| Approvals | CE, TUV, UL, CSA and FM |
Honeywell FS-TSDI-16UNI is a safety digital input field termination assembly for the Honeywell Safety Manager. It terminates sixteen 24/48 VDC or NAMUR input channels in two fused groups of eight.
Honeywell FS-TSDI-16UNI provides fused field termination and routing for sixteen universal safe digital input channels.
Honeywell FS-TSDI-16UNI is used with SDIL-1608 modules for 24/48 VDC or NAMUR safety inputs in standard Safety Manager cabinets.
Honeywell specifies sixteen inputs, two fused groups, 250 mA fuses, 175 mA maximum output per fuse and 90 x 70 x 60 mm dimensions.
Honeywell FS-TSDI-16UNI connects through SICC-0001/Lx to one or a redundant pair of approved SDIL-1608 modules.
Before installing Honeywell FS-TSDI-16UNI, verify the complete model and revision, mounting arrangement, power, field wiring, grounding and approved Safety Manager configuration.
Commission Honeywell FS-TSDI-16UNI under the approved Honeywell and site procedure. Prove its configured channels, diagnostics, communications and safety response before returning the system to service.
Do not substitute a similar suffix for Honeywell FS-TSDI-16UNI until the hardware revision, electrical interface, companion assembly and Safety Manager release are confirmed compatible.
Provide the complete Honeywell FS-TSDI-16UNI nameplate, version, serial number, companion hardware, Safety Manager release, quantity and destination.
Send the complete model, version, quantity, destination and nameplate photo. We will verify identification before confirming availability and lead time.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.
Copyright @2026 SalesPlc Limited. Sitemap
/ Blog
/ XML
/ Terms And Conditions
/ Privacy Policy
Network Supported