4200N
Primary Remote Extender Module · Primary RXM · Multimode · 375 kbps · Up to 2 km
Lifecycle note: Preserve primary RXM assignment, optical-loss measurements and three-channel fiber routing. Retain the complete 4200N qualification and revision record.
ItemNO:
4200NProduct Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcPrimary Remote Extender Module · Tricon Nuclear Equipment
Triconex 4200N is the primary remote-extender module identity listed in the manufacturer nuclear-equipment cross-reference. The corresponding standard 4200 belongs to the multimode RXM arrangement. A primary RXM set supports optical communication to as many as three remote RXM chassis.
The documented multimode interface operates at 850 nm over 62.5/125 micrometre fiber using ST connectors. I/O communication is 375 kbps. The 2 km maximum distance is conditional on the optical budget, including connector and splice losses; the manual gives 8 dB worst case rather than treating the 15 dB typical value as guaranteed margin.
Keep the distinction between an individual 4200N module and the 4200-3N set on the purchase order. Confirm primary-chassis assignment, three-channel fiber routing and the associated remote equipment before installation. Technical correspondence to standard hardware does not replace the qualification records for the N-suffix assembly.
| Manufacturer | Triconex |
|---|---|
| Model | 4200N |
| Manufacturer cross-reference | Nuclear 4200N corresponds to standard 4200 |
| Module role | Primary remote extender module (RXM) |
| Set distinction | 4200N is a module; 4200-3N is the listed set |
| Remote capacity | Primary RXM set supports up to three remote RXM chassis |
| I/O communication rate | 375 kbps |
| Fiber type | 62.5/125 µm multimode |
| Optical wavelength | 850 nm |
| Maximum optical distance | 2 km, subject to optical-loss budget |
| Connector | ST |
| Fiber attenuation reference | 4 dB/km worst case |
| Optical power budget | 15 dB typical; 8 dB worst case, including connector losses |
| Channel cabling | TX/RX fiber pair per channel; preserve three-channel routing |
Preserve primary RXM assignment, optical-loss measurements and three-channel fiber routing. Retain the complete 4200N qualification and revision record.
The manufacturer specifies support for up to three remote RXM chassis from the primary set. Confirm the installed topology and I/O allocation; this is a set-level capability, not a count of spare modules supplied.
Not by the model designation alone. The nuclear-equipment table separately lists 4200N and 4200-3N. State whether the request is for an individual module or a full set and confirm the offered quantity.
The manual gives 15 dB typical and 8 dB worst case, including transmitter, receiver and connector losses. Use the applicable worst-case design basis and measured installed losses rather than assuming the typical margin.
The installation guide describes separate routes for the three channels to reduce common physical damage. Preserve the approved channel separation and spare-fiber arrangement when replacing an RXM.
No. The optical link and the local electrical segment have separate limits. The guide identifies a 100-foot (30-metre) local electrical limit; assess each segment against its own requirements.
No. The corresponding 4200 multimode specification uses 850 nm and 62.5/125 micrometre fiber. Single-mode RXM models are separate equipment identities.
The guide requires at least one configured I/O module in an RXM chassis. Check the complete chassis population and the approved system configuration rather than treating the extender as an independent network switch.
Record the 4200N assembly revision, channel and remote-chassis assignment, optical loss results and required qualification evidence. This keeps the primary-end role traceable after the exchange.
Send the model, complete part number, quantity, destination and nameplate photo. We will verify identification details before confirming availability and lead time.
Manufacturer PDF extract: 4200N — Sales PLC Cover & Triconex Documentation. File size is below 1 MB; verify the exact installed hardware and configuration before use.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.
Copyright @2026 SalesPlc Limited. Sitemap
/ Blog
/ XML
/ Terms And Conditions
/ Privacy Policy
Network Supported