8312
230 VAC Chassis Power Module - Redundant Tricon Chassis Power Supply
Lifecycle note: Use the unit nameplate and current Triconex documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 15359408275230 VAC Chassis Power Module - Tricon Safety System
Triconex 8312 is a 230 VAC power module for supported Tricon main, expansion and remote extender chassis. The module converts plant AC input into regulated backplane power for processor, communication and I/O modules.
Historical Tricon planning documentation lists an input range of 185–285 VAC at 47–63 Hz, 175 W output capacity and a regulated 6.5 VDC backplane output rated up to 27 A at 60 °C.
Tricon chassis can use redundant power modules so a single supply fault does not require an immediate system shutdown. Replacement must match the 230 VAC variant, chassis generation, connector and redundancy arrangement; do not substitute a different input-voltage model.
| Manufacturer | Triconex |
|---|---|
| Model | 8312 |
| Order number | 8312 |
| Product type | Redundant Tricon Chassis Power Supply |
| System family | Tricon Safety System |
| Module type | Tricon chassis power module |
| Nominal input | 230 V AC |
| Input range | 185 to 285 V AC, 47 to 63 Hz |
| Rated output power | 175 W |
| Backplane output | 6.5 V DC ±1% |
| Maximum output current | 27 A at 60 °C |
| Chassis applications | Main, expansion and RXM chassis |
| Output hold time | 20 ms minimum at loss of input |
| Input fuse | 2.5 A time-delay |
| Status indicators | PASS, FAULT, ALARM, TEMP and BAT LOW |
Triconex 8312 is a 230 VAC chassis power module for supported Tricon main, expansion and remote extender chassis.
Triconex 8312 is documented for 185–285 VAC at 47–63 Hz, with a nominal 230 VAC supply.
Historical Tricon documentation lists 175 W capacity and a regulated 6.5 VDC backplane output up to 27 A at 60 °C.
Do not substitute by appearance. Confirm the 230 VAC input variant, chassis generation, module revision and redundant power arrangement.
Verify isolation, input voltage, fuse, chassis slot, connector condition, grounding and the identity of the companion power module.
Confirm PASS status, absence of FAULT, ALARM, TEMP or BAT LOW indications, stable chassis power and successful safety-system diagnostics.
Provide the complete 8312 nameplate, revision, chassis type, input supply, companion power-module model, quantity and destination.
Use Schneider Electric registered Triconex support and the installed Tricon planning documentation. No exact current public Schneider Electric datasheet was located.
Send the complete Triconex model, order number, revision, quantity, destination and nameplate photo. We will verify identification details before confirming availability and lead time.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.