9761-210
16-Point Current Input Termination Panel - 0-5 VDC Current-Input Termination Panel
Lifecycle note: Use the unit nameplate and current Triconex documentation as final references before approving a replacement.
Product Condition
Original New with One Year WarrantyParts Available
In Stock and Same Day ShippingDelivery Mode
Shipping via DHL Fedex or UPS etcEmail:
sales17@amikon.cnWhatsapp/Mob:
+86 1535940827516-Point Current Input Termination Panel - Tricon Safety System
Triconex 9761-210 is a 16-point current-input termination panel for supported Tricon analog input arrangements. Each field loop is terminated on the panel so the loop current can be presented to the compatible input module as a 0-5 VDC signal.
The documented circuit uses a 250-ohm precision input resistor for each channel and a 180-ohm series resistor in each positive transmitter-power path. Redundant 24 VDC supplies are combined through diode ORing for the field-loop power arrangement.
Before installation, verify transmitter polarity, channel numbering, loop-power source, panel cable and the exact analog input module. Recommission each loop and compare the measured engineering value with the safety-system configuration.
| Manufacturer | Triconex |
|---|---|
| Model | 9761-210 |
| Order number | 9761-210 |
| Product type | 0-5 VDC Current-Input Termination Panel |
| System family | Tricon Safety System |
| Input points | 16 |
| Input application | Current input converted to 0-5 VDC |
| Power output terminals | 16 positive terminals |
| Current input terminals | 16 negative terminals |
| Series resistance | 180 ohm in each positive power terminal |
| Precision input resistance | 250 ohm for each current input |
| Loop power | Redundant 24 VDC supplies with diode ORing |
| Installation check | Two-wire transmitter polarity, loop supply, cable and channel map |
Triconex 9761-210 provides 16 current-input termination points.
Triconex 9761-210 uses a 250-ohm precision input resistor so the supported current loop is represented as a 0-5 VDC input signal.
Triconex 9761-210 provides positive power terminals with 180-ohm series resistance and supports redundant 24 VDC supplies through diode ORing.
Confirm every transmitter positive lead, current-return lead and the redundant supply polarity against the approved loop drawing.
Match the panel, analog input module, interface cable, signal range, transmitter type and channel allocation.
Verify loop supply, continuity, measured current, converted input value, channel mapping and the approved safety response.
Provide the complete 9761-210 label, revision, connected I/O module, cable number, transmitter type, quantity and photographs.
Use Schneider Electric support documentation and the installed field-termination and loop drawings as final references.
Send the complete Triconex model, order number, revision, quantity, destination and nameplate photo. We will verify identification details before confirming availability and lead time.
Visit us
32D Guomao Building, No.388, Hubin South Road, Siming DistrictDisclaimer : Salesplcauto sells new and surplus products and develops channels for purchasing such products. This website has not been approved or recognized by any of the listed manufacturers or trademarks. Salesplcauto is not an authorized distributor, dealer, or representative of the products displayed on this website. All product names, trademarks, brands, and logos used on this website are the property of their respective owners. The description, explanation, or sale of products with these names, trademarks, brands, and logos is for identification purposes only and is not intended to indicate any association with or authorization from any rights holder.